! Water tank heat control
! Assume constant volume (i.e. water in = water out)
!--------------------------------------------------------
CONFIGURATION
PLOT_DURATION = 100.0; ! seconds
SIM_SCHEDULE_RATE = 0.1; ! second
SIM_INC_RATE = 0.01; ! second
END_CONFIGURATION;
SEGMENT Control
CYCLE_TIME 0.50
! Name MIN MAX
IN Temperature(32.0, 212.0)
IN Water_out (0.0, 10.0)
IN Temp_error (-90.0, 90.0)
OUT Gas_valve (0.0, 10.0)
Initialization
Gas_valve = 0;
END;
! Name Below Low High Above Truth
Symbol Zero OF Water_out ( 0.0, 0.0, 0.0, 2.0, 1.0)
Symbol Light OF Water_out ( 0.0, 2.0, 3.0, 5.9, 1.0)
Symbol Medium OF Water_out ( 3.0, 5.0, 6.0, 8.0, 1.0)
Symbol Heavy OF Water_out ( 6.0, 8.0, 10.0, 10.0, 1.0)
Symbol VeryCold OF Temp_error(-90.0, -90.0, -30.0, -20.0, 1.0)
Symbol Cold OF Temp_error(-30.0, -20.0, -10.0, 0.0, 1.0)
Symbol OnTarget OF Temp_error(-10.0, 0.0, 0.0, 10.0, 1.0)
Symbol Hot OF Temp_error( 0.0, 10.0, 20.0, 30.0, 1.0)
Symbol VeryHot OF Temp_error( 20.0, 30.0, 90.0, 90.0, 1.0)
! Name Below Low High Above Truth Center
Symbol Off OF Gas_valve ( 0.0, 0.0, 0.0, 2.0, 1.0, 0.0)
Symbol VeryLow OF Gas_valve ( 0.0, 2.0, 2.0, 4.0, 1.0)
Symbol Low OF Gas_valve ( 2.0, 4.0, 4.0, 6.0, 1.0)
Symbol High OF Gas_valve ( 4.0, 6.0, 6.0, 8.0, 1.0)
Symbol VeryHigh OF Gas_valve ( 6.0, 8.0, 10.0, 10.0, 1.0, 10.0)
!!!!!!!! Rules for controlling Gas_valve
! Heavy Medium Light Zero
!--------------------------------------------
! VeryCold VH VH VH VH
! Cold VH H H L
! OnTarget L VL VL Off
! Hot Off Off Off Off
! VeryHot Off Off Off Off
!
!
IF Temp_error IS VeryCold
THEN Gas_valve IS VeryHigh
IF Temp_error IS Cold AND Water_out IS Heavy
THEN Gas_valve IS VeryHigh
IF Temp_error IS Cold AND Water_out IS Medium
THEN Gas_valve IS High
IF Temp_error IS Cold AND Water_out IS Light
THEN Gas_valve IS High
IF Temp_error IS Cold AND Water_out IS Zero
THEN Gas_valve IS Low
IF Temp_error IS OnTarget AND Water_out IS Heavy
THEN Gas_valve IS High
IF Temp_error IS OnTarget AND Water_out IS Medium
THEN Gas_valve IS Low
IF Temp_error IS OnTarget AND Water_out IS Light
THEN Gas_valve IS VeryLow
IF Temp_error IS OnTarget AND Water_out IS Zero
THEN Gas_valve IS Off
IF Temp_error IS Hot
THEN Gas_valve IS Off
IF Temp_error IS VeryHot
THEN Gas_valve IS Off
END Control;